C&I
Solis EverCore energy storage system 100–261 kWh · 30–125 kW
Solis EverCore (100–261 kWh / 30–125 kW) is an industrial containerised/outdoor battery energy storage system (BESS) for C&I facilities. It combines a high-voltage LiFePO₄ battery system with a powerful three-phase inverter to provide energy autonomy, peak shaving and uninterrupted operation for businesses.
Models
1 / 4
1 / 4
Overview
Solis EverCore (100–261 kWh / 30–125 kW) is an advanced All-in-One commercial and industrial energy storage system (Commercial & Industrial BESS) engineered for demanding energy applications in plants, factories, logistics complexes, agricultural enterprises, data centres and retail chains.
The system combines high-voltage battery arrays based on safe LiFePO₄ (lithium iron phosphate) chemistry, powerful conversion equipment (PCS), an intelligent thermal management system (liquid or forced-air cooling) and an integrated multi-level fire suppression system in a single protected enclosure. With its high energy density and flexible configuration in both power (30-125 kW) and capacity (100-261 kWh), EverCore makes it easy to build effective backup power systems and optimise electricity costs.
Solis EverCore supports peak shaving, valley filling, microgrid operation and full integration with solar power plants and industrial diesel generators. Fast response and transfer times protect continuous production processes from external grid disturbances, while remote management via SolisCloud delivers complete 24/7 control and diagnostics.
Key specifications
-
Battery voltage
High voltage — HV (200 V+)
-
Power range (kW)
30–125
Key features
-
An industrial all-in-one solution combining a high-voltage battery, inverter/PCS, climate control and fire suppression in a single enclosure
-
Safe, long-life LiFePO₄ cells rated for over 6,000–8,000 cycles for extended intensive operation
-
Flexible scaling in power (30–125 kW) and capacity (100–261 kWh) to match the individual needs of the site
-
Support for key C&I functions: Peak Shaving, Zero Export and microgrid control
-
Built-in multi-level fire suppression and climate control for maximum protection of property and equipment
-
High enclosure ingress protection (IP54/IP65) for reliable installation in open outdoor locations
-
Full integration with solar power plants and diesel generators to build uncompromising off-grid systems
-
Intelligent online monitoring and dispatch via SolisCloud with remote software updates (OTA)
Technical specifications
Models
SKU: EverCore-30kW-(30-125)kW-NV
System
- Rated system capacity
- 120.57 kWh
- Rated system capacity
- 120.57 kWh
- Rated system capacity
- 120.57 kWh
- Rated system capacity
- 120.57 kWh
- Rated system capacity
- 261.24 kWh
- Rated system capacity
- 261.24 kWh
- Rated system capacity
- 261.24 kWh
- Max. cycle rate
- 0.5 P
- Charge and discharge depth
- 100%
- Dimensions (W × H × D)
- 1250 × 2030 × 1540 mm
- Dimensions (W × H × D)
- 1250 × 2030 × 1540 mm
- Dimensions (W × H × D)
- 1250 × 2030 × 1540 mm
- Dimensions (W × H × D)
- 1250 × 2030 × 1540 mm
- Dimensions (W × H × D)
- 1850 × 2230 × 1600 mm
- Dimensions (W × H × D)
- 1850 × 2230 × 1600 mm
- Dimensions (W × H × D)
- 1850 × 2230 × 1600 mm
- Dimensions without inverter (W × H × D)
- 950 × 2030 × 1540 mm
- Dimensions without inverter (W × H × D)
- 950 × 2030 × 1540 mm
- Dimensions without inverter (W × H × D)
- 950 × 2030 × 1540 mm
- Dimensions without inverter (W × H × D)
- 950 × 2030 × 1540 mm
- Dimensions without inverter (W × H × D)
- 1400 × 2230 × 1600 mm
- Dimensions without inverter (W × H × D)
- 1400 × 2230 × 1600 mm
- Dimensions without inverter (W × H × D)
- 1400 × 2230 × 1600 mm
- Weight
- 1630 kg (Cabinet) + 73 kg (Inverter)
- Weight
- 1630 kg (Cabinet) + 73 kg (Inverter)
- Weight
- 1630 kg (Cabinet) + 73 kg (Inverter)
- Weight
- 1630 kg (Cabinet) + 73 kg (Inverter)
- Weight
- 2900 kg (Cabinet) + 170 kg (Inverter)
- Weight
- 2900 kg (Cabinet) + 170 kg (Inverter)
- Weight
- 2900 kg (Cabinet) + 170 kg (Inverter)
- Operating temperature range
- -25 ~ +55°C
- Storage temperature range
- 0 ~ +40°C
- Operating humidity range
- ≤ 95% (non-condensing)
- Max. operating altitude
- 4000 m
- System thermal management method
- Industrial-grade air-conditioning (Cabinet); Air cooling (Pack); Intelligent fan-cooling (Inverter)
Fire suppression and protection
- Ingress protection (IP)
- IP55 (Cabinet) + IP66 (Inverter)
- Anti-corrosion protection class (battery cabinet)
- C4/C5 (Optional)
- Anti-corrosion protection class (inverter)
- C5
- Noise level (rated operation)
- 70 dB(A) @ 1 m
- Noise level (rated operation)
- 70 dB(A) @ 1 m
- Noise level (rated operation)
- 70 dB(A) @ 1 m
- Noise level (rated operation)
- 70 dB(A) @ 1 m
- Noise level (rated operation)
- 75 dB(A) @ 1 m
- Noise level (rated operation)
- 75 dB(A) @ 1 m
- Noise level (rated operation)
- 75 dB(A) @ 1 m
- Lightning protection
- Type II (AC port), Type II (PV&Battery)
Protection
- Certification standards
- IEC62619, IEC61000-6-2/4, IEC62040, IEC63056, IEC62477, UN38.3
Battery
- Cell type
- LFP 3.2 V / 314 A·h
- Cell cycle life
- 8000
- System battery configuration
- 1P120S
- System battery configuration
- 1P120S
- System battery configuration
- 1P120S
- System battery configuration
- 1P120S
- System battery configuration
- 1P260S
- System battery configuration
- 1P260S
- System battery configuration
- 1P260S
- Rated voltage
- 384 V
- Rated voltage
- 384 V
- Rated voltage
- 384 V
- Rated voltage
- 384 V
- Rated voltage
- 832 V
- Rated voltage
- 832 V
- Rated voltage
- 832 V
- Operating voltage range
- 348 ~ 432 V
- Operating voltage range
- 348 ~ 432 V
- Operating voltage range
- 348 ~ 432 V
- Operating voltage range
- 348 ~ 432 V
- Operating voltage range
- 754 ~ 936 V
- Operating voltage range
- 754 ~ 936 V
- Operating voltage range
- 754 ~ 936 V
- Rated DC current
- 157 A
- Number of battery modules
- 6
- Number of battery modules
- 6
- Number of battery modules
- 6
- Number of battery modules
- 6
- Number of battery modules
- 13
- Number of battery modules
- 13
- Number of battery modules
- 13
- Battery module capacity
- 20.09 kWh
- Battery module weight
- 138 kg
Inverter
- Inverter model
- 80K10-NV- 100K10-NV- 125K10-NV-
- Rated output power
- 30 kW
- Rated output power
- 40 kW
- Rated output power
- 50 kW
- Rated output power
- 60 kW
- Rated output power
- 80 kW
- Rated output power
- 100 kW
- Rated output power
- 125 kW
- Max. apparent output power (on-grid)
- 30 kVA
- Max. apparent output power (on-grid)
- 40 kVA
- Max. apparent output power (on-grid)
- 50 kVA
- Max. apparent output power (on-grid)
- 60 kVA
- Max. apparent output power (on-grid)
- 80 kVA
- Max. apparent output power (on-grid)
- 100 kVA
- Max. apparent output power (on-grid)
- 125 kVA
- Rated grid voltage
- 3/N/PE, 220 V / 380 V; 3/N/PE, 230 V / 400 V
- Rated grid frequency
- 50 Hz / 60 Hz
- Grid frequency range
- 45 - 55 Hz / 55 - 65 Hz
- Rated output current
- 43.3 A
- Rated output current
- 57.7 A
- Rated output current
- 72.2 A
- Rated output current
- 86.6 A
- Rated output current
- 115.5 A
- Rated output current
- 144.3 A
- Rated output current
- 180.4 A
- Max. apparent output power (off-grid)
- 30-60K: 1.5 times of rated power, 10 s; 80-100K: 1.6 times of rated power, 10 s; 125K: 1.4 times of rated power, 10 s
- Backup switchover time
- < 10 ms
- Power factor
- > 0.99 (0.8 leading - 0.8 lagging)
- THDi / THDv (at linear load)
- < 2% / < 3%
- Recommended max. PV input power
- 60 kW
- Recommended max. PV input power
- 80 kW
- Recommended max. PV input power
- 100 kW
- Recommended max. PV input power
- 100 kW
- Recommended max. PV input power
- 160 kW
- Recommended max. PV input power
- 200 kW
- Recommended max. PV input power
- 250 kW
- Maximum input voltage
- 1000 V
- Rated voltage
- 600 V
- Start-up voltage
- 180 V
- MPPT voltage range
- 150 - 850 V
- MPPT voltage range
- 150 - 850 V
- MPPT voltage range
- 150 - 850 V
- MPPT voltage range
- 150 - 850 V
- MPPT voltage range
- 150 - 950 V
- MPPT voltage range
- 150 - 950 V
- MPPT voltage range
- 150 - 950 V
- MPPT voltage range at full load
- 600 - 850 V
- MPPT voltage range at full load
- 600 - 850 V
- MPPT voltage range at full load
- 600 - 850 V
- MPPT voltage range at full load
- 600 - 850 V
- MPPT voltage range at full load
- 550 - 900 V
- MPPT voltage range at full load
- 550 - 900 V
- MPPT voltage range at full load
- 550 - 900 V
- Max. input current
- 3 × 42 A
- Max. input current
- 4 × 42 A
- Max. input current
- 4 × 42 A
- Max. input current
- 4 × 42 A
- Max. input current
- 10 × 42 A
- Max. input current
- 10 × 42 A
- Max. input current
- 10 × 42 A
- Max. short-circuit current
- 3 × 60 A
- Max. short-circuit current
- 4 × 60 A
- Max. short-circuit current
- 4 × 60 A
- Max. short-circuit current
- 4 × 60 A
- Max. short-circuit current
- 10 × 60 A
- Max. short-circuit current
- 10 × 60 A
- Max. short-circuit current
- 10 × 60 A
- Number of MPPTs / max. inputs per MPPT
- 3 / 6
- Number of MPPTs / max. inputs per MPPT
- 4 / 8
- Number of MPPTs / max. inputs per MPPT
- 4 / 8
- Number of MPPTs / max. inputs per MPPT
- 4 / 8
- Number of MPPTs / max. inputs per MPPT
- 10 / 20
- Number of MPPTs / max. inputs per MPPT
- 10 / 20
- Number of MPPTs / max. inputs per MPPT
- 10 / 20
Communication
- Max. number of parallel units (on-grid / off-grid)
- 10
Documentation and certificates
-
DownloadDatasheet
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт.pdf
-
DownloadUser manual 1
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_інструкція.pdf
-
DownloadUser manual 2
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_інструкція2.pdf
-
DownloadUser manual 3
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_інструкція3.pdf
-
DownloadUser manual 4
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_інструкція4.pdf
-
DownloadCertificate 1
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_сертифікат.pdf
-
DownloadCertificate 2
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_сертифікат2.pdf
-
DownloadCertificate 3
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_сертифікат3.pdf
-
DownloadCertificate 4
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_сертифікат4.pdf
-
DownloadCertificate 5
Система накопичення Solis EverCore 100–261 кВт·год · 30–125 кВт_сертифікат5.pdf
Frequently asked questions
-
Start from the site's average daily consumption and the peak load the inverter has to carry in off-grid mode. The power range of each modification and the recommended PV array size for it are listed in the product card under "Key specifications" — for a precise selection, contact a Solis dealer or use the form below.
-
The list of validated batteries is published on the product page — in the compatible-equipment section, where one has already been compiled for that model. The voltage range (LV or HV, depending on the series) is stated in the technical specifications either way. If there is no list, or the battery you need is not on it, contact the Solis Ukraine technical department — compatibility should be confirmed separately.
-
Most Solis hybrid and off-grid inverters support connecting a generator with automatic start-up when the battery is discharged. Whether a specific model has this function, and how it is wired, is stated under "Key features" and in the "Technical specifications" table of the product card.
-
It depends on the series: single-phase models are designed for a 220 V grid, three-phase models for 380/400 V. The exact connection type for a given product is stated in the "Grid phases" card under "Key specifications".
-
Solis equipment carries the manufacturer's warranty, which in Ukraine is administered by official dealers and authorised service centres. The exact term and conditions are stated on the warranty card and on the device's rating plate — for registration and the claim procedure, see the Support section.
Didn't find your answer?
The Solis Ukraine technical department advises on equipment compatibility, wiring diagrams and system configuration.